MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
164 Manual, 03/2018, L1V30535632002A-01
Commands (use with MODBUS function 06)
4F00H 1
Enable remote variable 1
4F01H 1
Enable remote variable 2
4F02H 1
Enable remote variable 3
4F03H 1
Enable remote variable 4
4F04H 1
Enable remote variable 5
4F05H 1
Enable remote variable 6
4F06H 1
Enable remote variable 7
4F07H 1
Enable remote variable 8
2F00H 1
Change of operating mode
2F0AH 1
Simulation of pressing a key on the user interface
2F03H 1
Value 01h: Memory in EEPROM
Value 05h: Save and reboot
2F07H 1
Value 01h: Reset the ATC6300 and save in FRAM
2FF0H 1
Execution of the command menu
Value 01h: Save the setting of the real-time clock
If you write AAh in the corresponding address, the remote variable is set to 1. If you enter
BBh, the remote variable is set to 0 and disabled accordingly.
② Changing the operating mode
The following values must be sent to the address 2F00H in order to set the corresponding
operating mode: