Functions
5.1 Basic functions
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
55
The following table lists the available commands:
Reset maintenance interval hours 1
Reset maintenance interval hours 2
Reset maintenance operations 1
Reset maintenance interval for operating cycles 1
C04 Reset maintenance operations 2 Advanced Reset maintenance interval for operating cycles 2
Reset general counters CNTx
Sets the generic counter CNTx to zero
C06 Reset LIMx limits User Resets the status of the retained LIMx limits
C07 Reset hours counter Line 1 / Line 2 Advanced Resets the hours counter for the presence / ab-
sence of Line 1 and Line 2 within the respective
C08 Reset hour counters Breaker 1 /
Advanced Resets the hour counters for the closing / opening
processes of breakers 1 and 2
C09 Reset breaker operation Advanced Resets the counting of operating cycles for break-
Deletes the list of historical events
C11 Reset default parameters Advanced Resets all the parameters in the setup menu to
C12 Save parameters in backup memory Advanced Stores a copy of the currently set parameters in a
backup memory, so that they can be restored at a
C13 Reload parameters from backup
memory
Advanced Transfers the parameters stored in the backup
memory to the memory of the active settings
C14 Forced I/O Advanced Enables test mode so you can manually energize
any output.
In this mode, the installation technician has
sole responsibility for the control of the outputs
C15 Reset A03 - A04 alarms Advanced Restores the opening or closing command of the
switching devices after generating the alarms A03
C16 Simulates line failure Advanced The device switches to the AUT mode and for two
minutes simulates the failure of the priority line.
After this, it performs a load switchover as pro-