Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
123
The parameters for enabling / disabling the password are described below.
For entering the password, please refer to chapter Password protection (Page 36)
Note
Note the password
Please make a note of the new password that has been entered. Loss of this password
means that the device can no longer be parameterized. Please contact Technical Support if
you have lost t
he password.
Designation on ATC
display
P03.01 Password Password Enabling the password protection
– If this parameter is set to OFF, no password protection is
enabled. This means that all parameters can be changed
ON OFF-ON
P03.02 User password User level password
– Under this parameter and in connection with parameter
P03.01 a numeric code is set for the user level password.
(See chapter Password protection (Page 36))
1000 0-9999
P03.03 Advanced password Advanced level password
– Under this parameter and in connection with parameter
P03.01 a numerical code is set for the advanced level
password. (See chapter Password protection (Page 36))
2000 0-9999
P03.04 Remote password Remote password
– Under this parameter a numerical code is set for the
password for remote access via MODBUS. This is inde-
pendent from the parameter P03.01.
3000 OFF/1-9999