Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
85
Key features of the 3WL, frame size 1-3:
Compatible with standard for
transfer switching equipment
IEC60947-6-1 IEC60947-6-1 IEC60947-6-1
Rated operational voltage U
e
AC 50
/ 60 Hz
[V AC] 480
1
480
1
480
1
Rated operational current I
n
at 50 °C
[A] 1000 ... 2000 800 ... 1600 4000 ... 6300
Utilization category according to IEC
AC-32B AC-32B AC-32B
Rated operational frequency
Short-time withstand current I
cw
at 1s
2
2
2
Impulse withstand voltage (U
imp
) of
[kV] 12 12 12
Impulse withstand voltage (U
imp
) of
[kV] 2.5
3
2.5
3
2.5
3
Reduction due to maximum nominal voltage U
n
of the ATC6300 controller of 480 V AC
Dependent on the breaking capacity of the 3WL, see manual or catalog for further information.
3
For the motor operator, the U
imp
is 1.2 kV
Compatible with standard for trans-
IEC60947-6-1 IEC60947-6-1
Rated operational voltage U
e
AC 50
[V AC] 480
1
480
1
Rated operational current I
n
at 50 °C
[A] 400 ... 1600 630 ... 4000
Utilization category according to IEC
AC-32B AC-32B
Rated operational frequency
Short-time withstand current I
cw
at
[kA] 35
2
/ 50 66
Impulse withstand voltage (U
imp
) of
[kV] 12 12
Reduction due to maximum nominal voltage U
n
of the ATC6300 controller of 480 V AC
2
Applies to Ecoline. For further information, see the manual of the 3WT air circuit breaker.