Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
87
Operating times of the 3VL
Contact trans-
fer time, off-
time*
ms 1100 200 1100 200 1100 200 1100
ms 1000 5000 1000 5000 1000 5000 1000
Time I-O-II (for
min parame-
ter)*
ms 2100 5200 2100 5200 2100 5200 2100
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Contact transfer time,
off-time*
ms 300 1100 350 1100 350 5100 5100
Time I-O-II (for min
parameter)*
ms 5300 2100 5350 2100 5350 10100 10100
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position
Operating times of the 3WL
Contact transfer time,
off-time*
ms 180 200 200
Time I-O-II (for min
parameter)*
ms 253 273 273
* Comprises the minimum delay time from Line I to Line II of 100 ms (see parameter P05.03) in the OFF position