Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
126 Manual, 03/2018, L1V30535632002A-01
Designation on ATC
display
P05.07 Switching devices Type of switching device
– This parameter specifies whether the pro-
grammable Open / Close outputs must be con-
tinuously active (application with contactors or
with switching devices without feedback) or
operating in the pulse mode, i.e. enabled until
the switching device is located in the correct
position. If the pulse mode is selected, the
command is extended for a certain time (see
P5.08 and P5.09), even after the position has
Brk. Pul. Brk. Pul.
Brk. Con.
Chg. Pul.
Chg. Con.
Contactors
P05.08 Opening pulse dur. Opening pulse duration
– Minimum duration of an opening command
pulse. In the application using circuit breakers
with motor operators, a sufficiently long time
must be set in order to enable the complete
charging of the springs. This time is also taken
into consideration when operating in the contin-
s 10 1-600
P05.09 Closing pulse dur. Closing pulse duration
– Pulse duration of the closing pulse.
s 1 1-600
P05.10 Cont. command in
OFF
Continuous command in the RESET / OFF
mode
– This specifies the behavior of the open-
ing/closing command outputs in the continuous
signal mode, if the ATC6300 is in the
RESET / OFF mode. Used in applications with
contactors.
OFF – Opens the command outputs
NOC – Leaves the outputs unchanged
NOC OFF
NOC
P05.11 Load no powered
tim.
Maximum time during which the load has no
power - response delay for Alarm A07
– If both power supplies are simultaneously
unavailable for longer than the time set in
P5.11, alarm A07 is triggered.
s 60 OFF/1…3600
P05.12 Inh. aut. ret. pr. line Inhibits the automatic return to the priority line
– If this parameter is enabled, the supply is not
automatically switched back from the secondary
line to the priority line when it becomes availa-
ble again. Instead, it must be switched back
manually.
OFF – Disabled
ON – Lock enabled
OFF OFF/ON
P05.13 EJP mode EJP mode
Normal = Standard mode in the AUT mode.
Normal Normal
EJP
3)
EJP-T
4)
5)