Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
131
Designation on ATC
display
P06.08 Pres.del. Line 2 OK Presence delay (when Line 2 source available)
– Is used if the load on Line 2 can be connect-
ed.
Normally this time is longer than P6.07, as the
load is being energized,
and it is possible to
wait longer before considering voltage steadily
s 60 1-6000
P06.09 Phase failure thresh Threshold limit for phase failure
– Voltage threshold below which a phase loss
intervention occurs,
usually quicker than the drop. The delay for the
phase failure is specified by P06.10.
% 70 60 - 80
OFF
P06.10 Phase failure delay Delay time for the phase failure threshold limit
s 0.1 0.1 s-30 s
P06.11 Max. asymmetry
limit
Maximum limit for asymmetry of the phases
P06.11 specifies the upper threshold for
phase asymmetry referred to nominal voltage,
and P06.12 defines the related intervention
delay.
This measurement can be disabled by setting
% 15 1 % - 20 %
OFF
P06.12 Max asymmetry
delay
Delay time for maximum asymmetry of the
phases
- see Parameter 06.11
s 5 0.1-900
P06.13 Max frequency limit Limit for the maximum frequency
% 105 100-120
P06.14 Max frequency
Delay time for the maximum frequency s 3 0-600
P06.15 Min frequency limit Limit threshold for minimum frequency (can be
disabled)
- Maximum frequency intervention delay.
% 95 OFF
80-100
Delay time for minimum frequency
P06.17 Line cont. OFF
mode
Setting of the voltage measurement in the OFF
mode
OFF OFF
1)
ON
2)
OFF+GLOB
3)
4)
P06.18 Line cont. MAN
mode
Line cont. MAN mode
- As for Parameter 06.17, but referred to the
MANUAL mode
OFF OFF
ON
OFF+GLOB