Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
133
P07 Pa-
rameter
Line 2
Designation on ATC
display
Description
Unit
Default
Range
P07.09 Phase failure thresh Threshold limit for phase failure % 70 60 80
OFF
P07.10 Phase failure delay Delay time for the phase failure threshold limit
s 0.1 0.1 s - 30 s
P07.11 Max. asymmetry
limit
Maximum limit for asymmetry of the phases % 15 1 % -
20 % / OFF
P07.12 Max asymmetry
delay
Delay time for maximum asymmetry of the
phases
s 5 0.1 - 900
P07.13 Max frequency limit Limit for the maximum frequency % 105 100 -
120 / OFF
P07.14 Max frequency
delay
Delay time for the maximum frequency s 3 0 - 600
P07.15
Min frequency limit
Limit for minimum frequency
%
95
OFF / 80 - 100
P07.16
Min frequency delay
Delay time for minimum frequency
s
5
0 - 600
P07.17 Line cont. OFF
mode
Setting of the voltage measurement in the OFF
mode
OFF OFF
ON
OFF+GLOB
ON+GLOB
P07.18 Line cont. MAN
mode
Line 2 control in MAN mode OFF OFF
ON
OFF+GLOB
ON+GLOB
P07.19 Generator start
delay
Delay of generator start after failure of Line 2 s OFF OFF / 1 - 6000
P07.20
Cooling time
Generator cooling time
s
120