EasyManua.ls Logo

Siemens SENTRON ATC6300 - Page 152

Siemens SENTRON ATC6300
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODBUS communication
11.3 MODBUS ASCII protocol
3KC ATC6300 transfer control device
150 Manual, 03/2018, L1V30535632002A-01
Example:
In order, for example, to read the current voltage value of Line 1 between L3-L1 (0Ch) of a
slave using the serial address 08, the following message must be sent:
:
08
04
00
0B
00
02
E7
CRLF
: = ASCII 3Ah Message Start delimiter
08 = Address of the slave
04 = MODBUS function Read Input Register
00 0B = Address of the register (L3 voltage); reduced by 1
00 02 = Number of registers to be read, starting at Address 04
E7 = LRC Checksum
CRLF = ASCII 0Dh0Ah = Message end delimiter
The following reply is sent by the ATC6300:
: 08 04 04 00 00 01 90 9B CRLF
: = ASCII 3Ah Message Start delimiter
08 = ATC address (Slave 08)
04 = Function requested by the master
04 = Number of bytes sent by the multimeter
00 00 01 90 = Hexadecimal value of the voltage of Line 1 L3-L1 = 400 V
9B = LRC Checksum
CRLF = ASCII 0Dh0Ah = Message End delimiter

Table of Contents

Related product manuals