MODBUS communication
11.4 MODBUS functions
3KC ATC6300 transfer control device
152 Manual, 03/2018, L1V30535632002A-01
LSB register 10h 00h
The response always consists of the address of the slave, the code of the function that was
queried by the master, and the content of the queried register. The message is concluded by
the CRC Checksum .
Function 06: Preset single register
This function permits writing to the register. It can only be used with registers that have an
address greater than 1000 Hex. It is possible, for example, to modify parameters. If the new
parameter is not within the range of the ATC an error message is output. An error message
is also output in the case of incorrect parameter addresses. The addresses and the valid
parameter range can be found in the chapter Data library (Page 157).
The response of the slave is an echo to the query.
The slave sends the address and the new value of the parameter back to the master.
Function 07: Read exception status
Using this function, the status of the ATC6300 can be queried.