Siemens SENTRON ATC6300 - Changing Parameters via MODBUS

Siemens SENTRON ATC6300
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MODBUS communication
11.9 Changing parameters by means of MODBUS
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
171
Step 1: Select menu 08
Master
Function
= 6
Address
= 5000H (5000H - 0001H = 4FFFH)
Value
= 8 (08H)
01
06
4F
FF
00
08
AE
E8
ATC
Function
= 6
Address
= 5000H (5000H - 0001H = 4FFFH)
Value
= 8 (08H)
01
06
4F
FF
00
08
AE
E8
Step 2: Select submenu 01
Master
Function
= 6
Address
= 5000H (5000H - 0001H = 4FFFH)
Value
= 1 (01H)
01
06
50
00
00
01
59
0A
ATC
Function
= 6
Address
= 5001H (5001H - 0001H = 5000H)
Value
= 1 (01H)
01
06
50
00
00
01
59
0A