EasyManua.ls Logo

Siemens SENTRON ATC6300 - Page 62

Siemens SENTRON ATC6300
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
5.2 Extended functions
3KC ATC6300 transfer control device
60 Manual, 03/2018, L1V30535632002A-01
Example:
A user limit LIM1 of the voltage V L1-N of Line 1 is to be defined. The upper limit should be
250 V AC, and the lower limit should be 220 V AC.
Setting:
LIM1 Reference measurement: V L1-N
Source: Line 1
Channel number: 1
Function: Min + Max
Upper limit: 250 V
Multiplier: 1
Delay: 0.0 s
Lower limit 220 V
Multiplier: 1
Delay: 0.0 s
You can find a more detailed description in chapter P13 - Limit thresholds (Page 140).
See also
Description of the display pages (Page 24)

Table of Contents

Related product manuals