Connection
7.2 Connection of the power supply
3KC ATC6300 transfer control device
72 Manual, 03/2018, L1V30535632002A-01
Connecting the dual network connection
See the table below for the requirements of the supply lines needed for the connection:
CU
Cable diameter
V
e
= 240 V AC
V
imp
= 4 kV
0.5 ... 2.5 mm
2
AWG 20 - 14
I
e
= 3 A
0.5 ... 1.5 mm
2
AWG 20 - 16
1. Connect the dual network connection (3KC9625-1) using the appropriate tool as shown
in the diagram.
Connection drawing
F1
1x 3NW6003
-1
1x 3NW7013
10 A, gG