Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
83
7. Rated impulse withstand voltage
8. Switch position of the TSE
The following table lists the required data of the air circuit breakers and molded case circuit
breakers.
eck the data of the circuit breaker used against the corresponding catalog or manual.
Take the required data for the RTSE variants PC, 3KC3 and 3KC4 from the corresponding
manual or catalog.
Take the required data for the RTSE variants PC, 3KC3 and 3KC4 from the corresponding
manual or catalog.
Compatible with
standard for trans-
fer switching
IEC60947-
6-1
IEC60947-
6-1
IEC60947-
6-1
IEC60947-
6-1
IEC60947-
6-1
IEC60947-
6-1
IEC60947-
6-1
1
1
Rated operational
voltage U
e
AC 50 /
[V AC] 480
3
480³ 480³ 480³ 480³ 480³ 480³
Rated operational
current I
n
at 50 °C
ambient tempera-
[A] 16 … 160 16 … 250 25 … 100 25 … 160 160 … 250 250 … 400 400 … 630
Utilization catego-
ry according to
AC-32B AC-32B AC-32B AC-32B AC-32B AC-32B AC-32B
Rated operational
frequency
[Hz] 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60 50 / 60
Short-time with-
stand current I
cw
[kA] 2
2
3
2
n.a. n.a. n.a. n.a. n.a.
Impulse withstand
voltage (U
imp
) of
[kV] 8 8 8 8 8 8 8
Impulse withstand
voltage (U
imp
) of
[kV] 4 4 4 4 4 4 4
PC if the 3VA is used as a switch disconnector
Applies to 3VA switch disconnector
3
Reduction due to maximum nominal voltage U
n
of the ATC6300 controller of 480 V AC