Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
91
Note
According to IEC regulations, the fusible element must be connected via a cable compliant
with IEC
61439-1 which is protected against ground faults and short circuits. To this end,
please observe the applicable national standards for electrical installations.
Note
The connection diagram shows a typical connection of the ATC with 3VA The connection
diagram is va
lid for 230 V AC. All SEO drives can be used. For this purpose the relevant
technical specifications of the drive, the circuit breaker and the ATC6300 have to be
observed. You can find more information on the technical specifications in the corresponding
m
anuals.
General setting
Table: Output function
Table: Input function
Param-
eter
Setting Con-
nection
Param-
eter
Setting Con-
nection
Param-
eter
Setting
P05.07 Chg.
Pul.
25 P11.04.
01
Open Line 1 circuit
breaker
15 P10.01.
01
Line 1 breaker closed (feedback 1)
27 P11.05.
01
Close Line 1 circuit
breaker
16 P10.02.
01
Line 2 breaker closed (feedback 2)
28 P11.06.
01
Open Line 2 circuit
breaker
17 P10.03.
01
Line 1 circuit breaker protection (Trip
1)
30 P11.07.
01
Close Line 2 circuit
breaker
18 P10.04.
01
Line 2 circuit breaker protection (Trip
1)
If the 3VA molded case circuit breaker is used in combination with an SEO, the following
minimum parameters must be observed:
P05.06 Delay,
feedback signal
P06.07 Delay,
voltage present
P06.08 Delay,
Line 2 OK
P07.07 Delay,
voltage present
P07.08 Delay,
Line 1 OK
3VA22
2 s
2 s
2 s
2 s
2 s