Connection
7.3 Connection of Siemens SENTRON switching devices
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
91
Note
According to IEC regulations, the fusible element must be connected via a cable compliant
with IEC
61439-1 which is protected against ground faults and short circuits. To this end,
please observe the applicable national standards for electrical installations.
Note
The connection diagram shows a typical connection of the ATC with 3VA The connection
diagram is va
lid for 230 V AC. All SEO drives can be used. For this purpose the relevant
technical specifications of the drive, the circuit breaker and the ATC6300 have to be
observed. You can find more information on the technical specifications in the corresponding
m
anuals.
Param-
Setting Con-
Param-
Setting Con-
Param-
Setting
P05.07 Chg.
25 P11.04.
Open Line 1 circuit
15 P10.01.
Line 1 breaker closed (feedback 1)
27 P11.05.
Close Line 1 circuit
16 P10.02.
Line 2 breaker closed (feedback 2)
28 P11.06.
Open Line 2 circuit
17 P10.03.
Line 1 circuit breaker protection (Trip
30 P11.07.
Close Line 2 circuit
18 P10.04.
Line 2 circuit breaker protection (Trip
If the 3VA molded case circuit breaker is used in combination with an SEO, the following
minimum parameters must be observed:
P05.06 Delay,
feedback signal
P06.07 Delay,
voltage present
P07.07 Delay,
voltage present