Function DPV0
de‐
vice
S7 DP
device
DPV1
device
Comment
• Time stamping
--- X X
1
If you congure the ET 200iSP with the GSD le (in HW Cong), then you need SIMATIC PDM for the
parameter assignment.
2
With the S7 DP device, diagnostic and hardware interrupts are only signaled when the CPU is in RUN
mode.
DPV0
"DPV0" mode designates a mode for communication between devices on the PROFIBUS.
The mode includes the basic functions of the PROFIBUS DP communication protocol
• Cyclic data exchange between control system and devices
• Conguration via GSD les
• Diagnostics
DPV1
"DPV1" mode is a further development of the original PROFIBUS standard IEC 61784-1:2002 Ed1
CP 3/1.
DPV1 designates a mode for communication between devices on the PROFIBUS.
The mode extends the functions of the PROFIBUS DP communication protocol compared to
"DPV0" mode. The changes are specied in the IEC 61158 standard:
• Acyclic data exchange between control system and devices
• Integration into engineering systems via EDD or FDT / DTM
• Transferable PLC software function blocks (IEC 61131‑3)
• Fail‑safe communication (PROFIsafe)
• Interrupts (hardware interrupt, status interrupt, update interrupt, vendor-specic interrupt,
diagnostic interrupt, plug interrupt, pull interrupt)
7.3 Project engineering with STEP 7
Properties
• The ET 200iSP is included in the STEP 7 hardware catalog.
• Diagnostic interrupts, hardware interrupts, pull/plug interrupts (only for S7-400) and time
stamping are supported.
Commissioning and Diagnostics
7.3 Project engineering with STEP 7
ET 200iSP
160 Operating Instructions, 11/2022, A5E00247483-AK