Network interface module
12
12.1 PROFINET interface module IM 152-1PN
Article number
6ES7152-1BA00-0AB0
Properties
The interface module IM 152-1PN has the following properties:
• Operation as IO device
• Preparing the data for the installed electronic modules
• The PROFINET IO conguration can be set via the network.
• Switching o the DC 24 V supply voltage at the terminal module TM-PS-A also switches o
the interface module.
• The maximum address space is 244 bytes for inputs and 244 bytes for outputs.
• Update rmware via PROFINET IO
• Redundancy
• Connecting the station of the ET 200iSP to PROFINET IO via ber-optic cables (up to 3 km in
length)
• Redundant connection (MRP, S2, R1 system redundancy)
• Backing up the parameters of the electronic modules:
– The parameters / data are saved in the interface module.
• Startup
– After switching on the power supply of the station, the interface module distributes the
saved parameters/data to the electronic modules (e.g. substitute values for the output
modules).
– Next, the connection to the network is enabled and the automation system is
commissioned by the IO controller.
– Only when the station exchanges data with the IO controller are the substitute values (of
the ash memory) replaced with the actual data of the IO controller.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 277