14.12.6 HART warning
Description
If you enable this parameter, then a diagnostic interrupt is triggered for the following HART
warnings (see Error types of the electronic modules with PROFIBUS (Page 209)):
HART additional status available
HART con󹪝guration changed
14.12.7 HART diagnostics
Description
If you enable this parameter, a diagnostic interrupt is triggered for the following HART
diagnostics (see Error types of the electronic modules with PROFIBUS (Page 209)):
HART analog output current speci󹪝ed
HART analog output current saturated
HART communication error
HART primary variable outside of the limits
HART non-primary variable outside of the limits
Analog electronic modules
14.12 Parameter description of the analog electronic modules
ET 200iSP
410 Operating Instructions, 11/2022, A5E00247483-AK