3.14 Removing and inserting of modules
Pulling and plugging digital electronics module 8 DI NAMUR
1. Swing the rst of the three 8 DI NAMUR electronic modules out from the terminal module
during operation.
2. Observe the status LEDs.
For PROFINET conguration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
– ER: on (means: LED lights up)
– MT: o (means: LED does not light up)
– ACT: On
– RN: On
– PS1: On, PS2: O
– LK1 and/or LK2: on (when a network connection is set up from one device to another;
otherwise o)
For PROFIBUS conguration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
– SF: on --> diagnostic message is available.
– BF: O
– ON: On
– PS1: On, PS2: O
Result: The ET 200iSP continues operating without fault.