6. Save the changes (menu command File > Save) to update the 󹪝le.
7. Load all parameters into the modules (menu command Device > Full download to device).
Exit SIMATIC PDM.
Reference
You can 󹪝nd additional information on the parameter assignment in the documentation and
online help of SIMATIC PDM.
7.5 Assigning Parameters for the ET 200iSP during Operation using
SIMATIC PDM
Properties
You can con󹪝gure the modules during operation using SIMATIC PDM. Each new parameter
assignment that is correct is applied by the module and retentively stored.
Incorrect parameters are ignored. The module remains in the previous con󹪝guration state.
Restarting the modules (after supply voltage of the ET 200iSP o󹪜 ---> on) results in the
currently retentively stored con󹪝guration being applied in the modules: LED "SF" of the
electronic modules o󹪜
Applying the retentively stored con󹪝guration in the modules is independent of the
communication of the ET 200iSP to the higher-level component (IO controller/DP master).
The outputs of the modules are controlled by the higher-level components (IO controller/
Class 1 DP master).
Requirements
PROFINET: SIMATIC PDM as of V9.2.2 (integrated or "stand alone" version)
PROFIBUS: SIMATIC PDM as of V6.0 (integrated or "stand alone" version)
Procedure for re-con󹪝guration
1. Start SIMATIC PDM.
2. Open the project.
3. Switch the view in the SIMATIC Manager: Menu command View > Process Network View.
4. Select the desired ET 200iSP module in the left part of the window. Select "Open objects" in
the shortcut menu. Result: SIMATIC PDM starts.
5. Load the parameters and/or I&M of the module into the PG/PC.
6. Change the parameters and/or I&M.
Commissioning and Diagnostics
7.5 Assigning Parameters for the ET 200iSP during Operation using SIMATIC PDM
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 165

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals