7. Select the remote I/O object created in the previous step (ET 200iSP), select Insert new
object > Remote I/O module in the shortcut menu. In the following dialog box, enter:
Name: Designation for the module (e.g. 8 DI NAMUR).
Address: Slot of the 1st electronic module in the ET 200iSP station.
Number of "Remote I/O" objects: Number of electronic modules in the ET 200iSP station.
Conrm with "OK". Result: The electronic modules are now displayed in the right-hand pane
of the window.
8. Select the rst remote I/O object (electronic module in the left pane of the SIMATIC Manager),
select Open objects in the shortcut menu. In the following dialog box "SIMATIC PDM device
selection" select SIEMENS > ET 200iSP > Modules and conrm with "OK".
9. In the following dialog box, select "Specialist" as the user and conrm with "OK". In this mode,
you can assign parameters. Result: SIMATIC PDM starts.
10.After SIMATIC PDM has been started, select the corresponding electronic module as "Module
type". Then click in one of the gray elds to update the window. Result: The parameters and
I&M of the electronic module are displayed.
11.Now set the parameters of the electronic module. Save the changes with the menu
command File > Save and download the parameters with the menu command Device
> Download to device in the electronic module. Exit SIMATIC PDM.
12.For each of the ET 200iSP objects (electronic modules), proceed as described in points 8 to
11.
Procedure for assigning parameters to the interface module
1. Select the remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager), select Open
objects in the shortcut menu.
In the following dialog box "SIMATIC PDM device selection" select SIEMENS > ET 200iSP
> Header-end and conrm with "OK".
2. In the following dialog box, select "Specialist" as the user and conrm with "OK". In this mode,
you can assign parameters. Result: SIMATIC PDM starts.
3. Now set the parameters of the interface module. Save the changes with the menu
command File > Save and download the parameters to the interface module with the menu
command Device > Download to device. Exit SIMATIC PDM.
Procedure for parameter assignment of all modules of the ET 200iSP
1. Select the remote I/O object (ET 200iSP in the left pane of the SIMATIC Manager), select Open
objects in the shortcut menu.
2. In the following dialog box "SIMATIC PDM device selection" select SIEMENS > ET 200iSP
> Header-end and conrm with "OK".
3. In the following dialog box, select "Specialist" as the user and conrm with "OK".
4. Load all parameters of the modules (menu command File > Full upload to PG/PC).
5. Set the parameters for all required modules. In the left pane of SIMATIC PDM you can navigate
to all modules of the ET 200iSP.
Commissioning and Diagnostics
7.4 Project Engineering with GSD File and SIMATIC PDM
ET 200iSP
164 Operating Instructions, 11/2022, A5E00247483-AK