3.12 Putting the Example into Operation
Commissioning
1. Switch on the power supply of the ET 200iSP.
2. Observe the status LED at the S7-400 and at the ET 200iSP:
LEDs of the CPU:
– RUN: on (means: LED lights up)
– All other LEDs: o (means: LED does not light up)
For PROFINET conguration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
– ER: O
– MT: O
– ACT: O
– RN: on
– PS1: On, PS2: O
– LK1 and/or LK2: on (when a network connection is set up from one device to another;
otherwise o)
For PROFIBUS conguration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
– SF: O
– BF: O
– ACT: O
– ON: on
– PS1: On, PS2: O
3.13 Evaluating the diagnostics
Evaluating the diagnostics
If an error occurs, OB82 is started. Evaluate the startup information in OB82.
Tip: Call the SFC13 within the OB82 and evaluate the diagnostics frame from section
"Commissioning and Diagnostics (Page 155)".
Commissioning guideline
3.13 Evaluating the diagnostics
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 55