Con󹪝guration "2 Count/ 6 Control"
With this con󹪝guration, you can also control the counters over the digital inputs.
Assignment of the digital inputs at the electronic module 8 DI NAMUR
You can 󹪝nd more information on the pin assignment in the technical speci󹪝cations of the
electronic module 8 DI NAMUR.
Table 4-13 Assignment of the digital inputs for 2 Count/ 6 Control
Digital input Terminal Assignment
Channel 0 1, 2 Counter 1
Channel 1 5, 6 Counter 2 (does not apply to 32-bit down counters)
Channel 2 9, 10 control signal GATE 1
Channel 3 13, 14 control signal GATE 2
Channel 4 3, 4 control signal Reset counter 1
Channel 5 7, 8 control signal Reset counter 2
Channel 6 11, 12 control signal Reset counter output 1
Channel 7 15, 16 control signal Reset counter output 2
Assignment of the process image inputs (PII)
The assignment is identical to the "2 Count/ 6 DI NAMUR" con󹪝guration.
Assignment of the process image outputs (PIQ)
The assignment is identical to the "2 Count/ 6 DI NAMUR" con󹪝guration.
4.17.4 Assigning parameters to counters
Procedure in HW Con󹪝g
Double-click with the mouse on the electronic module 8 DI NAMUR in the con󹪝guration table
and start the parameter assignment.
Con󹪝gurations (principle)
4.17 Counting
ET 200iSP
96 Operating Instructions, 11/2022, A5E00247483-AK