LEDs Meaning Remedy
SF BF ACT ON
on O * on Data exchange between the ET 200iSP and
the DP master, there is at least one diagnos‐
tic and/or one deviation from the nominal
and actual conguration.
Check the process wiring.
Check the electronic modules.
Check the preset and actual conguration
(missing or wrong module).
* on * on No connection with the DP master (baud
rate search):
Cause:
Communication via the network is interrup‐
ted.
Check the bus (is the bus connector inser‐
ted correctly).
Check the terminating resistor and the
RS 485‑IS coupler.
* Flashes * on IM 152-1DP is incorrectly congured - there
is no data exchange between the DP master
and the ET 200iSP.
Causes:
Wrong network address.
Inconsistent preset and actual congura‐
tion.
Faults in the network.
Check the conguration (network address).
Check the preset and actual conguration
(missing or wrong module).
Check the bus conguration (bus connec‐
tor, terminating resistor, RS 485‑IS coupler).
on O * on Invalid network address.
• PROFIBUS DP address 126 or 127 set.
• PROFIBUS DP address changed without
deleting retentive data.
For PROFIBUS DP
• Set a valid PROFIBUS DP address on the
IM 152-1DP.
• If you have changed the PROFIBUS DP
address, then delete the retentive data.
on on * O Delete retentive data
• Switch on with PROFIBUS DP address "0".
---
O Flash‐
es at
0.5 Hz
* O Retentive data is deleted, turn o. Set the desired network parameters/
addresses before switching on the next
time.
* O on on The IM 152-1DP is exchanging data with
the higher-level bus component and the
electronic modules of the ET 200iSP. In re‐
dundancy mode, this IM 152-1DP is the ac‐
tive module of the ET 200iSP.
---
* O O on Voltage is applied to the IM 152-1DP. In re‐
dundancy mode, this IM 152-1DP is
the passive module, i.e. there is no data
exchange with the electronic modules.
---
Flashes
at 0.5
Hz
**
O O on In redundancy mode, this IM 152-1DP is
the passive module, and not ready for
bumpless switchover (for example, associ‐
ated CPU in STOP).
Bring the H-system to the redundant state.
Flashes
2 Hz
Flashes
2 Hz
Flash‐
es
2 Hz
Flash‐
es
2 Hz
The IM 152-1DP is in the safe state. Pull and plug the IM 152-1DP. If the ash
code continues to occur, contact Siemens
Support.
* Not applicable
** After the transition to redundant operation, the SF LED ashes for another 20 s.
Commissioning and Diagnostics
7.9 Status and error LEDs on the IM 152-1DP
ET 200iSP
174 Operating Instructions, 11/2022, A5E00247483-AK