Parameter Range of values Default Applicability
Output range
Disabled
0 to 20 mA
4 to 20 mA
HART
HART Channel
Response to CPU/ master STOP
Zero output cur‐
rent/voltage
Use substitute val‐
ue
Keep last value
Use substitute val‐
ue
Channel
Substitute value Every value of the
nominal range
0 to 20 mA: 0 mA
4 to 20 mA and
HART: 4 mA
Channel
WARNING
The substitute values are stored in the 󹪞ash memory of the interface module. These are output
at the next startup of the ET 200iSP until the ET 200iSP exchanges data with the DP master.
Note this behavior when changing the ET 200iSP to another con󹪝guration environment.
Remedy: Delete the 󹪞ash memory of the interface module beforehand.
Parameters for con󹪝guration "...I +x"
In addition to the "4 AO I HART" con󹪝guration, the following parameters can be set in the "...I +x"
con󹪝gurations:
Table 14-43 Parameters for con󹪝guration "I +x"
Parameter Range of values Default Applicability
HART retries (number of retries) 0 to 10 2 Module
HART Fast Mode
Enabled
Disabled
Disabled Module
Channel
0
1
2
3
0 Channel
IEEE variable,
None
Primary variable
1st non-primary variable
2nd non-primary variable
3rd non-primary variable
None Channel
Analog electronic modules
14.11 Parameters of the analog electronic modules
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 405

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals