Parameter Range of values Default Applicability
Output range
• Disabled
• 0 to 20 mA
• 4 to 20 mA
• HART
HART Channel
Response to CPU/ master STOP
• Zero output cur‐
rent/voltage
• Use substitute val‐
ue
• Keep last value
Use substitute val‐
ue
Channel
Substitute value Every value of the
nominal range
0 to 20 mA: 0 mA
4 to 20 mA and
HART: 4 mA
Channel
WARNING
The substitute values are stored in the ash memory of the interface module. These are output
at the next startup of the ET 200iSP until the ET 200iSP exchanges data with the DP master.
Note this behavior when changing the ET 200iSP to another conguration environment.
Remedy: Delete the ash memory of the interface module beforehand.
Parameters for conguration "...I +x"
In addition to the "4 AO I HART" conguration, the following parameters can be set in the "...I +x"
congurations:
Table 14-43 Parameters for conguration "I +x"
Parameter Range of values Default Applicability
HART retries (number of retries) 0 to 10 2 Module
HART Fast Mode
• Enabled
• Disabled
Disabled Module
Channel
• 0
• 1
• 2
• 3
0 Channel
IEEE variable,
• None
• Primary variable
• 1st non-primary variable
• 2nd non-primary variable
• 3rd non-primary variable
None Channel
Analog electronic modules
14.11 Parameters of the analog electronic modules
ET 200iSP