4. Analyze the diagnostic message.
Result for PROFINET con󹪝guration:
Identi󹪝er-related diagnostics: Bit 7.3 is set -> Slot 2
Slot: 2
Subslot: 1
Channel fault type: 6 - Wire break
Result for PROFIBUS con󹪝guration:
Station status 1 (byte 0): Bit 3 is set -> External diagnostics
Identi󹪝er-related diagnostics: Bit 7.3 is set -> Slot 4
Channel-related diagnostics:
Byte 25: 10000011
B
-> Slot 4
Byte 26: 01000000
B
-> Channel 0
Byte 27: 00110
B
-> Wire break
5. Connect the cable to the BERO back to terminal 1 and analyze the diagnostics again:
Result:
For PROFINET con󹪝guration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
ER: O󹪜
For PROFIBUS con󹪝guration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
SF: O󹪜
Status LEDs electronic module 8 DI NAMUR:
SF: O󹪜
3: o󹪜/on
The diagnostic message has been deleted.
Commissioning guideline
3.15 Wire break of NAMUR encoder on digital input module
ET 200iSP
58 Operating Instructions, 11/2022, A5E00247483-AK

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals