Alarms, faults and system messages
11.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
213
Upgrade firmware or contact technical support.
F01018 Power-up aborted more than once After this fault is output, the converter powers up with the factory settings.
Remedy: Back up factory setting with p0971=1. Switch CU off and on
again. Recommission the converter.
F01040 Parameters must be saved Save parameters (p0971).
Switch CU off and on again.
F01044 Loading of memory data card de-
Replace memory card or CU.
Reduce number of data records.
Contact technical support.
F01512 An attempt has been made to
establish an conversion factor for
scaling which is not present
Create scaling or check transfer value.
F01662 CU hardware fault Switch CU off and on again, upgrade firmware, or contact technical sup-
Power Module: Monitoring U
CE
Check or replace the Power Module.
Incorrect Power Module data
Replace Power Module or upgrade CU firmware.
Replace the Power Module.
F30662 CU hardware fault Switch CU off and on again, upgrade firmware, or contact technical sup-
F30664 CU power up aborted Switch CU off and on again, upgrade firmware, or contact technical sup-
F30850 Software fault in Power Module Replace Power Module or contact technical support.
Table 11- 3 The most important alarms and faults
F01018 Power-up aborted more than once
1. Switch the module off and on again.
2. After this fault has been output, the module is booted with the factory
settings.
3. Recommission the inverter.
A01028 Configuration error Explanation: Parameterization on the memory card has been created with
a different type of module (article number).
Check the module parameters and recommission if necessary.
F01033 Switching over units: Reference
Set the value of the reference parameter not equal to 0.0 (p0304, p0305,
p0310, p0596, p2000, p2001, p2002, p2003, r2004).
F01034 Switching over units: Calculation of
the parameter values after refer-
ence value change unsuccessful
Select the value of the reference parameter so that the parameters in-
volved can be calculated in the per unit notation (p0304, p0305, p0310,
p0596, p2000, p2001, p2002, p2003, r2004).
Motor maintenance interval lapsed
Carry out maintenance and reset the maintenance interval (p0651).