Alarms, faults and system messages
11.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
214 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
A01910
F01910
Fieldbus SS setpoint timeout The alarm is generated when p2040 ≠0 ms and one of the following
causes is present:
• The bus connection is interrupted
• Communications error (CRC, parity bit, logical error)
• An excessively low value for the fieldbus monitoring time (p2040)
A01920 PROFIBUS: Cyclic connection
interrupt
Explanation: The cyclic connection to PROFIBUS master is interrupted.
Establish the PROFIBUS connection and activate the PROFIBUS master
Check that the sensor is connected correctly.
A05000
A05001
A05002
A05004
Power Module overtemperature Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
F06310 Supply voltage (p0210) incorrectly
set
Check the set supply voltage and if required change (p0210).
F07011 Motor overtemperature Reduce the motor load.
Check ambient temperature.
Check the wiring and connection of the sensor.
A07012 I2t Motor Module overtemperature Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check thermal time constant p0611.
Check overtemperature fault threshold p0605.
A07015 Motor temperature sensor alarm Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
F07016 Motor temperature sensor fault Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Deactivate the motor temperature sensor fault evaluation (p0607 = 0).
F07086
Switching over units: Parameter
Check the adapted parameter values and if required correct.
F07320 Automatic restart aborted Increase the number of restart attempts (p1211). The actual number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
A07321 Automatic restart active Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is auto-
matically switched back on.
Search current measured too low
Increase search current (p1202), check motor connection.
A07409 U/f control, current limiting control-
ler active
The alarm automatically disappears after one of the following measures:
• Increase the current limit (p0640).
• Reduce the load.
• Slow down the up ramp for the setpoint speed.