Alarms, faults and system messages
11.6 List of alarms and faults
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
215
F07413 Commutation angle incorrect (pole
position identification)
An incorrect commutation angle can result in positive feedback in the
speed controller.
Check the motor phase sequence (wiring, p1820).
Adjust the encoder.
Replace the encoder.
Carry out pole position identification.
F07426 Technology controller actual value
limited
• Adapt the limits to the signal level (p2267, p2268).
• Check the actual value scaling (p2264).
F07801 Motor overcurrent Check current limits (p0640).
Vector control: Check current controller (p1715, p1717).
U/f control: Check the current limiting controller (p1340 … p1346).
Increase acceleration ramp (p1120) or reduce load.
Check motor and motor cables for short-circuit and ground fault.
Check the motor regarding the star/delta connection and rating plate
parameterization.
Check power unit / motor combination.
Select flying restart function (p1200) if switched to rotating motor.
A07805 Drive: Power unit overload I2t
• Reduce the continuous load.
• Adapt the load cycle.
• Check the assignment of rated currents of the motor and power unit.
F07806 Regenerative power limit exceeded Increase deceleration ramp.
Reduce driving load.
Use power unit with higher energy recovery capability.
For vector control, the regenerative power limit in p1531 can be reduced
until the fault is no longer activated.
F07807 Short-circuit detected
• Check the inverter connection on the motor side for any phase-phase
short-circuit.
• Rule out that line and motor cables have been interchanged.
A07850
A07851
A07852
External alarm 1 … 3 The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for
the external alarm 1… 3.
Remedy: Remove the causes of these alarms.
F07860
F07861
External fault 1 … 3 Remove the external causes for this fault.
F07900 Motor blocked Check that the motor can run freely.
Check the torque limits (r1538 and r1539).
Check whether the motor is overloaded.
F07902 Motor stalled Check whether the motor data has been set correctly and perform a mo-
tor identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.