Configure the hardware
5.3 Configure the hardware in SIMATIC Manager
SIMATIC ET 200pro FC-2 converter
Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
65
3. If you have configured an F-RSM, configure the start address of the process image and
configure the group diagnostics.
4. Add an inverter to the right of the F-switch or F-RSM.
5. Set the addresses of the inputs and outputs of the frequency converter.
You have configured a fail-safe inverter.
Set up the PROFIsafe address on the F-switch
If you are using an F-switch, you must set up the PROFIsafe address on the module and
configure it in STEP 7.
Figure 5-7 Setting the PROFIsafe address 1018 by way of example
The switch positions 0000000000 and 1111111111 are not allowed!