Commissioning
6.5 Basic commissioning
SIMATIC ET 200pro FC-2 converter
76 Operating Instructions, 04/2015, FW V4.7.3, A5E34257324B AB
11.
Input the correct Motor Speed from the motor rating
plate.
This value is given in RP
M.
12.
Select to run or
disable Motor Data Identification func-
tion.
This function, if active, will not start until the first run
command is given to the Inverter.
13.
Set the Minimum Speed at which the attached motor
should run.
14.
Set the Ramp Up time in seconds.
This is the time the Inverter/motor system will take from
being given the run command, to reaching the selected
motor speed.
15.
Set the Ramp Down time in seconds.
This is the time the Inverter/motor system will take from
being given the OFF1 command, for the motor to reach
a standstill.