Basics of program execution
8.2 Asynchronous instructions
Distributed I/O system
146 System Manual, 09/2019, A5E03576849-AJ
Difference between synchronous/asynchronous instructions
The figure below shows the difference between processing an asynchronous instruction and
processing a synchronous instruction. In this figure the asynchronous instruction is called
five times before the execution is completed, for example, a data record is completely
transferred.
With a synchronous instruction, the instruction is fully executed in each call.
First call of the asynchronous instruction, start of processing
Intermediate call of asynchronous instruction, continuation of processing
Last call of the asynchronous instruction, termination of processing
The synchronous instruction is completely processed at each call
Duration of the complete processing
Figure 8-1 Difference between synchronous and asynchronous instructions

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals