Technical specifications
14.5 Mechanical and climatic environmental conditions
Distributed I/O system
282 System Manual, 09/2019, A5E03576849-AJ
14.5 Mechanical and climatic environmental conditions
Operating conditions
The ET 200SP distributed I/O system is suitable for use in weather-proof, fixed locations.
The operating conditions are based on the requirements of DIN EN 60721-3-3:1995 +
A2:1997:
Class 3M3 (mechanical requirements)
Class 3K3 (climatic requirements)
You will find the permissible ambient conditions for the motor starter in the Technical data of
the motor starter (https://support.industry.siemens.com/cs/ww/en/ps/21859/td
).
Mechanical environmental conditions
The following table shows the mechanical environmental conditions in the form of sinusoidal
vibrations.
Table 14- 8 Mechanical environmental conditions
Frequency band
ET 200SP with IM 155-
6 DP HF, BusAdapters
BA 2×FC, BA 2xSCRJ,
BA SCRJ/FC, BA 2xLC
and BA LC/FC
ET 200SP with
BusAdapters BA 2×RJ45,
BA SCRJ/RJ45 and BA
LC/RJ45
ET 200SP with
IM 155-6 PN BA
ET 200SP with digital
output module F-RQ
1x24VDC/24..230VAC/5A
5 f 8.4 Hz
3.5 mm amplitude
8.4 f 150 Hz
1 g constant acceleration
10 f 60 Hz
0.35 mm amplitude
--- --- ---
60 f 1000 Hz 5 g constant acceleration