Commissioning
11.11 Identification and maintenance data
Distributed I/O system
226 System Manual, 09/2019, A5E03576849-AJ
11.11 Identification and maintenance data
11.11.1 Reading out and entering I&M data
I&M data
Identification and maintenance data (I&M data) is information saved on the module. The data
is:
Read-only (I-data) or
Readable/writable (M-data)
Identification data (I&M0): Manufacturer information about the module that can only be read.
Some identification data is also printed on the housing of the module, for example article
number and serial number.
Maintenance data (I&M1, 2, 3): Plant-dependent information, e.g. installation location.
Maintenance data is created during configuration and downloaded to the module.
All modules of the ET 200SP distributed I/O system support identification data (I&M0 to
I&M3).
The I&M identification data supports you in the following activities:
Checking the plant configuration
Locating hardware changes in a plant
Correcting errors in a plant
Modules can be clearly identified online using the I&M identification data.
STEP 7 allows you to read the identification I&M data (see STEP 7 online help).
Note
The BusAdapter and the interface module IM
155-6 PN HF support the identification data
I&M0 to I&M4 (signature).
Options for reading out I&M data
Via the user program
Via STEP 7 or HMI devices
Via the CPU web server

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals