Commissioning
11.2 Commissioning the ET 200SP for PROFINET IO
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
197
Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an I-device on the
PROFINET IO, we recommend the following procedure:
Table 11- 2 Procedure for commissioning the ET 200SP as an I-device on the PROFINET IO
Step
Procedure
See ...
1
Installing ET 200SP
Section Installation (Page 63)
2 Connecting ET 200SP
Supply voltages
PROFINET IO
Sensors and actuators
Section Wiring (Page 86)
3 Inserting a SIMATIC memory card in the I-
device
Section Removing/inserting a SIMATIC
memory card on the CPU (Page 205)
4
Configuring the I-device
Section Configuring (Page 131)
5
Checking the protective measures
-
6 Switching on supply voltages for the IO
controller
Documentation of the IO controller
7 Switching on supply voltages for I-device
and IO devices
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
and documentation of the IO devices
8
Download configuration to the I-device
STEP 7 online help
9 Switching IO controller and I-device to RUN
mode
Documentation of the IO controller and
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
10 Checking LEDs CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
11 Testing inputs and outputs The following functions are helpful: Mon-
itoring and modifying tags, testing with
program status, forcing, controlling the
outputs. See section Test and service
functions (Page 258)

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200SP and is the answer not in the manual?

Siemens SIMATIC ET 200SP Specifications

General IconGeneral
System TypeDistributed I/O System
MountingDIN Rail
Communication ProtocolPROFINET, PROFIBUS
IP RatingIP20
CategoryI/O Systems
Supply Voltage24 V DC
ModularityYes
Hot SwappingYes
Storage Temperature-40°C to +70°C
Digital InputsYes
Digital OutputsYes
Analog InputsYes
Analog OutputsYes
Communication InterfacePROFINET, PROFIBUS
Number of ModulesUp to 64
Relative Humidity5 to 95% (non-condensing)
Operating Temperature-25°C to +60°C

Related product manuals