Commissioning
11.3 Commissioning the ET 200SP on PROFIBUS DP
Distributed I/O system
202 System Manual, 09/2019, A5E03576849-AJ
Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an I-slave on the
PROFIBUS DP, we recommend the following procedure:
Table 11- 5 Procedure for commissioning the ET 200SP as an I-slave for PROFIBUS DP
Installing ET 200SP (with CPU and CM DP)
Section Installation (Page 63)
2 Connecting ET 200SP
• Supply voltages
• PROFIBUS DP
• Sensors and actuators
Section Wiring (Page 86)
3 Configuring DP master (including
Documentation of the DP master
4 Inserting a SIMATIC memory card in the I-
Section Removing/inserting a SIMATIC
memory card on the CPU (Page 205)
5 Configuring I-slave (including PROFIBUS
address)
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) and CM
Switching on supply voltages for DP master
Documentation of the DP master
7 Switching on supply voltages for I-slaves CPU 15xxSP-1 PN
(
http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
8 Loading configuration in the DP master and
STEP 7 online help
9 Switching DP master and I-slaves to RUN Documentation of the DP master and
CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
10 Checking LEDs CPU 15xxSP-1 PN
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) manual
11 Testing inputs and outputs The following functions are helpful: Mon-
itoring and modifying tags, testing with
program status, forcing, controlling the
outputs. See the Test functions and fault
resolution
(http://support.automation.siemens.com/
WW/view/en/90466439/133300) section