EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Page 24

Siemens SIMATIC ET 200SP
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System overview
3.3 How are SIMATIC Safety F-systems structured with ET 200SP?
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
23
Achievable safety classes
The fail-safe modules are equipped with integrated safety functions for safety mode.
You can achieve the safety classes of the table below:
With the appropriate parameter assignment of the safety functions in STEP 7
With a specific combination of fail-safe and non-fail-safe I/O modules
With a special arrangement and wiring of the sensors and actuators
Table 3- 1 Safety classes that can be achieved with ET 200SP in safety mode
Safety class in safety mode
According to IEC 61508
In accordance with ISO 13849-1
SIL2
Category 3
(PL) Performance Level d
SIL3
Category 3
(PL) Performance Level e
SIL3
Category 4
(PL) Performance Level e
Additional information
You will find the use cases and wiring for the relevant safety class in the manuals of the fail-
safe I/Os and the fail-safe motor starters.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Related product manuals