Test and service functions
13.1 Test functions
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
261
Testing with watch tables
The following functions are available in the watch table:
Monitoring of tags
With watch tables, you can monitor the current values of individual tags of a user program
or a CPU on the PG/PC and Web server. For the Web server to be able to display the
value of tags, you must specify a symbolic name for each tag in the "Name" column of the
watch table.
You can monitor the following operand areas:
Inputs and outputs (process image) and bit memory
Contents of data blocks
Peripheral inputs and peripheral outputs
Timers and counters
Modifying tags
Use this function to assign fixed values to the individual tags of a user program or CPU.
Modifying is also possible for testing with program status.
You can control the following operand areas:
Inputs and outputs (process image) and bit memory
Contents of data blocks
Peripheral inputs and peripheral outputs (for example, %I0.0:P, %Q0.0:P)
Timers and counters
"Enable peripheral outputs" and "Control immediately"
These two functions enable you to assign fixed values to individual peripheral outputs of
a CPU in the STOP mode. You can also use them to check your wiring.