EasyManua.ls Logo

Siemens SIMATIC ET 200SP - Page 51

Siemens SIMATIC ET 200SP
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application planning
4.5 Forming potential groups
Distributed I/O system
50 System Manual, 09/2019, A5E03576849-AJ
Placement and grouping of I/O modules
Each BaseUnit BU...D that you install in the ET 200SP configuration opens a new potential
group and supplies all subsequent I/O modules (on BaseUnits BU...B) with the necessary
supply voltage. The first 24 V DC I/O module to the right of the CPU/interface module must
be installed on a light-colored BaseUnit BU...D. Exception: If you insert an AC I/O module or
an AI Energy Meter as the first I/O module, the first BaseUnit in the ET 200SP configuration
can be a dark-colored BaseUnit. The requirement is that you use a CPU or IM 155-6 (as of
V3.0).
If you want to place another BaseUnit BU...B after a BaseUnit BU...D, disconnect the power
and AUX buses and open a new potential group at the same time. This allows individual
grouping of the supply voltages.
Note
All BaseUnits placed in a load group must match the infeed potential of the corresponding
light
-colored BaseUnits.
Do not connect any BaseUnit of the "BU...B" type on the right of a motor starter's BaseUnit
(BU30-MSxx).
Placing and connecting potential distributor modules
Potential distributor modules provide potential distributors integrated into the system that you
can use to configure a rapid, space-saving customized replacement for standard potential
distribution systems.
You can place potential distributor modules at any location within the ET 200SP distributed
I/O system. To do so, you must observe the same design rules as for placing and connecting
I/O modules. Potential distributor modules are only suitable for SELV/PELV.
A potential distributor module consists of a potential distributor BaseUnit (PotDis-BU) and (if
necessary) a potential distributor TerminalBlock (PotDis-TB) plugged onto it. If you do not
need the additional terminals of the PotDis-TB, install a BU cover (15 mm) on the PotDis-
BaseUnit.
You must not place a BaseUnit for I/O modules in a PotDis potential group formed with a
light-colored PotDis-BaseUnit.
Note
Identical voltages with potential distributor modules
You can only connect identical (supplied) voltages with to the terminals of a potential
distributor module or PotDis potential group. Example: You only connect 24
V DC.

Table of Contents

Other manuals for Siemens SIMATIC ET 200SP

Related product manuals