8-29
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
Digital Output Module 4 24 V DC / 0.5 A (6ES5 441–8MA11)
pr93a030
Technical Specifications
Address ID for ET 200U
S DP Siemens
S DP Standard
8DQ or 017
8DQ or 032
Number of outputs
Galvanic isolation
S in groups of
8
no
8
Load voltage L+
S rated value
S permissible range
S (including ripple)
S value when t < 0.5 s
24 V DC
20 to 30 V
35 V
Warning: Capacitor C
remains loaded after
switch off of L+
!
Output current for “1” signal
S rated value
S permissible range
S lamp load
0.5 A at 60 _C /
1 A at 30 _C
5 mA to 1 A
max. 5 W
Resid. current at “0” signal
Output voltage
S “1” signal
max. 1 mA
max. L+ (– 1.2 V)
Total permissible current of
outputs
4 A
Short–circuit protection
Voltage induced on circuit
interruption (internal)
limited to
none
–15 V
Switching frequency
S resistive load
S inductive load
max. 100 Hz
max. 2 Hz
Driving of digital input possible
Paralleling of 2 outputs
S maximum current
possible
0.8 A
Length of cable
S unshielded
max. 100 m (330 ft.)
Rated isolation voltage*
(+9 V to )
S isolation group
12 V AC
1 B
Current consumption
S from +9 V (CPU)
S from L+ (without load)
typ. 14 mA
typ. 15 mA
Power loss of the module typ. 3.5 W
Weight approx. 220 g (7.7 oz.)
* Relevant only for ungrounded configuration in the
ET 200U
Module Spectrum

Table of Contents

Related product manuals