Commissioning
8.4 Operating modes
S7-1500 Automation System
104 System Manual, 01/2013, A5E03461182-01
Response when expected and actual configurations do not match
The expected configuration is represented by the configuration loaded into the CPU. The
actual configuration is the actual configuration of the automation system. If the expected
configuration and actual configuration deviate from one another, then the CPU's behavior is
specified by the setting of the hardware compatibility. For additional information about the
hardware compatibility, see the section Operating mode transition (Page 99).
Can
c
eling a startup
If errors occur during startup, the startup is canceled and the CPU remains in "STOP" mode.
Under the following conditions, a startup will not be performed or will be canceled:
If no SIMATIC memory card is inserted or an invalid one is inserted.
If no hardware configuration has been downloaded.
Parameter assignment of startup behavior
You can assign parameters for the behavior of the CPU in the "Startup" group of the CPU
properties. Additional information on configuring the startup behavior can be found in the
Operating mode transitions (Page 99) section.
8.4.3 "STOP" mode
Function
In the "STOP" operating mode the user program is not executed.
All outputs are disabled or react according to the parameter settings for the respective
module: They provide a substitute value as set in the parameters or retain the last value
output and thus hold the controlled process in a safe operating mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500 Automation System and is the answer not in the manual?

Siemens SIMATIC S7-1500 Automation System Specifications

General IconGeneral
SeriesSIMATIC S7-1500
ProgrammingTIA Portal (Totally Integrated Automation Portal)
Protection ClassIP20
CPUVarious models available (e.g., CPU 1511-1 PN, CPU 1518-4 PN/DP)
Controller TypeModular Controller
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
Digital InputsVaries by model and expansion modules
Digital OutputsVaries by model and expansion modules
Analog InputsVaries by model and expansion modules
Analog OutputsVaries by model and expansion modules
Backplane BusHigh-speed backplane bus for fast communication between modules
RedundancySupported with specific models and configurations
SafetyIntegrated safety functions available
ScalabilityHighly scalable with modular expansion
Operating Temperature0°C to 60°C

Related product manuals