Wiring
6.5 Connect supply voltage to the CPU
S7-1500 Automation System
60 System Manual, 01/2013, A5E03461182-01
6.5 Connect supply voltage to the CPU
Introduction
The supply voltage of the CPU is supplied by means of a 4-pole cable connector, which is
located on the front of the CPU.
Connection for supply voltage
The connections of the 4-pole connector have the following meaning:
/
/ 0
0
+ 24 V DC of the supply voltage
Mass of the supply voltage
Mass of the supply voltage for looping (current limited to 10 A)
+ 24 V DC of the supply voltage for looping (current limited to 10 A)
Spring opener (one spring opener per terminal)
Figure 6-3 Connection for supply voltage
The maximum connector cross-section is 1.5 mm
2
. The cable connector offers you the option
of looping the supply voltage uninterrupted, even when it is unplugged.
Requirements
Only wire the cable connector when the supply voltage is turned off.
Follow the wiring rules (Page 59).
Tools required
3 to 3.5 mm screwdriver
Tool-free connection of cables: multi-wire (stranded), with end sleeve or ultrasonic compressed
1. Strip 8 to 11 mm of the wires.
2. Seal or crimp the wire with end sleeves.
3. Insert the wire into the push-in terminal as far as it will go.
4. Push the wired connection plug into the plug socket of the CPU.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500 Automation System and is the answer not in the manual?

Siemens SIMATIC S7-1500 Automation System Specifications

General IconGeneral
SeriesSIMATIC S7-1500
ProgrammingTIA Portal (Totally Integrated Automation Portal)
Protection ClassIP20
CPUVarious models available (e.g., CPU 1511-1 PN, CPU 1518-4 PN/DP)
Controller TypeModular Controller
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
Digital InputsVaries by model and expansion modules
Digital OutputsVaries by model and expansion modules
Analog InputsVaries by model and expansion modules
Analog OutputsVaries by model and expansion modules
Backplane BusHigh-speed backplane bus for fast communication between modules
RedundancySupported with specific models and configurations
SafetyIntegrated safety functions available
ScalabilityHighly scalable with modular expansion
Operating Temperature0°C to 60°C

Related product manuals