EasyManuals Logo

Siemens SIMATIC S7-1500 Automation System User Manual

Siemens SIMATIC S7-1500 Automation System
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #94 background imageLoading...
Page #94 background image
Commissioning
8.2 Review before the first power-on
S7-1500 Automation System
94 System Manual, 01/2013, A5E03461182-01
8.2 Review before the first power-on
Review before the first power-on
Before the first power-on check the installation and the wiring of the S7-1500 automation
system.
Questions for the review
The following questions provide guidance for the review of your S7-1500 automation system
in the form of a checklist.
Racks
Are the mounting rails firmly installed on the wall, in the framework, or in the cabinet?
Are the cable ducts correctly installed?
Have the minimum clearances been observed?
Grounding and chassis concept
Is the mounting rail connected to the protective conductor?
Has the connection between reference ground and ground been correctly made on all
mounting rails?
Are the required equipotential bonding cables connected with low impedance to the
affected analog parts?
Module installation and wiring
Are all the modules inserted / installed in accordance with the mounting plan and
corresponding to the configuration with STEP 7 and screwed firmly to the mounting rail?
Are all the front connectors wired according to the circuit diagram, in the final position,
and inserted on the correct module?
Are the correct modules installed and connected to each other with U connectors?
Are U-connectors projecting either at the left-hand or right-hand over the outer modules
at the S7-1500 automation system?
System power supply or load current supply
Are all the system power supply and load current supply modules switched off?
Is the power cable connector correctly wired?
Has the connection to line voltage been made?

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500 Automation System and is the answer not in the manual?

Siemens SIMATIC S7-1500 Automation System Specifications

General IconGeneral
SeriesSIMATIC S7-1500
ProgrammingTIA Portal (Totally Integrated Automation Portal)
Protection ClassIP20
CPUVarious models available (e.g., CPU 1511-1 PN, CPU 1518-4 PN/DP)
Controller TypeModular Controller
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
Digital InputsVaries by model and expansion modules
Digital OutputsVaries by model and expansion modules
Analog InputsVaries by model and expansion modules
Analog OutputsVaries by model and expansion modules
Backplane BusHigh-speed backplane bus for fast communication between modules
RedundancySupported with specific models and configurations
SafetyIntegrated safety functions available
ScalabilityHighly scalable with modular expansion
Operating Temperature0°C to 60°C

Related product manuals