Wiring
6
6.1 Rules and regulations for operation
Introduction
As part of plants and/or systems, the S7-1500 automation system requires adherence to
special rules and regulations, depending on the field of application.
This section provides an overview of the most important rules that must be observed for the
integration of the S7-1500 CPU in a plant or system.
Specific application
Please observe the safety and accident prevention regulations applying to specific
applications (e.g., machine protection guidelines).
EMERGENCY-STOP devices
"EMERGENCY-STOP" devices in accordance with IEC 60204 (corresponds to
DIN VDE 0113) must remain effective in all operating modes of the plant or system.
Excluding hazardous plant states
No dangerous operating states may occur when
The CPU starts up again after a voltage dip or a power failure
The bus communication is resumed after a fault
If necessary, EMERGENCY-STOP must be forced!
An uncontrolled or undefined startup is not permitted after the EMERGENCY STOP is
unlocked.
Line voltage
Below is described, what you must pay attention to with respect to the supply voltage (see
the section Statements on insulation tests, protection classes, degree of protection, and
rated voltage
(Page 173)):
For fixe
d plants or systems without multipole circuit breaker, a mains disconnection
device (multipole) must be available in the building installation.
For all power circuits of the S7-1500 CPU, the fluctuation/deviation of the line voltage
from the rated value must be within the permitted tolerance.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500 Automation System and is the answer not in the manual?

Siemens SIMATIC S7-1500 Automation System Specifications

General IconGeneral
SeriesSIMATIC S7-1500
ProgrammingTIA Portal (Totally Integrated Automation Portal)
Protection ClassIP20
CPUVarious models available (e.g., CPU 1511-1 PN, CPU 1518-4 PN/DP)
Controller TypeModular Controller
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
Digital InputsVaries by model and expansion modules
Digital OutputsVaries by model and expansion modules
Analog InputsVaries by model and expansion modules
Analog OutputsVaries by model and expansion modules
Backplane BusHigh-speed backplane bus for fast communication between modules
RedundancySupported with specific models and configurations
SafetyIntegrated safety functions available
ScalabilityHighly scalable with modular expansion
Operating Temperature0°C to 60°C

Related product manuals