Commissioning
8.3 Commissioning procedure
S7-1500 Automation System
98 System Manual, 01/2013, A5E03461182-01
Reactions after removing/inserting the SIMATIC memory card
When inserting and removing the SIMATIC memory card, the CPU automatically performs
memory reset, and then goes into STOP mode.
The CPU evaluates the SIMATIC memory card, and indicates this by flashing the
RUN/STOP LED.
Reference
Additional information on the SIMATIC memory card can be found in the SIMATIC memory
card (Page 135) section.
8.3.2 First power-on
Introduction
The following procedure describes the commissioning of the CPU.
Requirements
An S7-1500 automation system is installed and wired
SIMATIC memory card has been inserted into the CPU
First power-on of a CPU
Switch on the system power supply and load power supply.
Result:
The CPU executes a flash test:
All LEDs flash at 2 Hz
RUN/STOP LED flashes alternately yellow/green
ERROR LED flashes red
MAINT LED flashes yellow
This is followed by system initialization with evaluation of the SIMATIC memory card:
RUN/STOP LED flashes yellow at 2 Hz
After the system initialization has been completed, the CPU goes to STOP mode:
The RUN/STOP LED lights up yellow

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500 Automation System and is the answer not in the manual?

Siemens SIMATIC S7-1500 Automation System Specifications

General IconGeneral
SeriesSIMATIC S7-1500
ProgrammingTIA Portal (Totally Integrated Automation Portal)
Protection ClassIP20
CPUVarious models available (e.g., CPU 1511-1 PN, CPU 1518-4 PN/DP)
Controller TypeModular Controller
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Communication InterfacesPROFINET, PROFIBUS, Ethernet, OPC UA
Digital InputsVaries by model and expansion modules
Digital OutputsVaries by model and expansion modules
Analog InputsVaries by model and expansion modules
Analog OutputsVaries by model and expansion modules
Backplane BusHigh-speed backplane bus for fast communication between modules
RedundancySupported with specific models and configurations
SafetyIntegrated safety functions available
ScalabilityHighly scalable with modular expansion
Operating Temperature0°C to 60°C

Related product manuals