EasyManua.ls Logo

Siemens SIMATIC S7-1500 Automation System

Siemens SIMATIC S7-1500 Automation System
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
6.8 Front connector for the I/O modules
S7-1500 Automation System
64 System Manual, 01/2013, A5E03461182-01
6.8 Front connector for the I/O modules
6.8.1 Characteristics of the front connector
Introduction
The sensors and actuators of your plant are connected to the S7-1500 automation system by
means of front connectors. Wire the sensors and actuators to the front connector and then
plug it into the I/O module. Wire the front connector in the "pre-wiring position" that makes
convenient wiring possible before you insert it into the I/O module.
The completely wired front connector can be removed easily from the I/O module and
replaced without a lot of effect when a module is replaced.
Characteristics of the front connector
Figure 6-6 Front connectors
The front connector is characterized by the following:
40 clamping points each
Clamping technology: Screw
If you want to supply load groups with the same potential (non-isolated), use the potential
bridges supplied for the front connector. In four locations: 9 and 29, 10 and 30, 19 and
39, 20 and 40, the terminals can be bridged by means of potential bridges. Advantage:
Reduction of the wiring effort.
Note
Note that the potential bridges may only be deployed with a maximum rated voltage of
24 VDC! The current capacity per potential bridge is 8 A maximum.

Table of Contents

Related product manuals