EasyManua.ls Logo

Siemens SIMATIC S7-1500 Automation System

Siemens SIMATIC S7-1500 Automation System
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
6.2 Operating the S7-1500 on grounded infeed
S7-1500 Automation System
System Manual, 01/2013, A5E03461182-01
55
6.2 Operating the S7-1500 on grounded infeed
Introduction
The following provides information on the overall configuration of an S7-1500 on a grounded
infeed (TN-S network). The specific subjects discussed are:
Disconnecting devices, short-circuit and overload protection to IEC 60364 (corresponding
to DIN VDE 0100) and IEC 60204 (corresponding to DIN VDE 0113).
Load power supplies and load circuits.
Grounded infeed
In the case of grounding incoming supplies (TN-S system) the neutral conductor (N) and the
protective conductor (PE) are each grounded. Both conductors form a part of the overvoltage
concept. When a plant is in operation, the current flows across the neutral conductor. When
a fault occurs, for example a single ground fault between a live conductor and ground, the
current flows through the protective conductor.
Safe electrical isolation (SELV/PELV in accordance with IEC 60364-4-41)
Load current supply modules / power supply modules with safe electrical isolation are
necessary for operating the S7-1500. This protection is designated as SELV (Safety Extra
Low Voltage)/PELV (Protective Extra Low Voltage) in accordance with IEC 60364-4-41.
Reference potential of the controller
The reference potential of the S7-1500 automation system is connected with the mounting
rail through a high-resistance RC combination. In this way, high-frequency interference
currents are conducted and electrostatic charges are avoided. Despite the grounded
mounting rail, the reference potential of the S7-1500 automation system has to be
considered as ungrounded due to the high-resistance connection.
If you want to configure the S7-1500 automation system with grounded reference potential,
connect the reference potential of the controller (M connection of the CPU) galvanically with
the protective conductor.
A simplified representation of the potential relationships is available in the chapter Electrical
config
uratio
n of the S7-1500 (Page 58).

Table of Contents

Related product manuals