Standard Functions
12.7 Safety Oriented Tripping
SIMOCODE PRO V PN FDI
104 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
DM-F Local
Description
Sensor input automatic start /
moni
tored start
Automatic start:
The enabling circuits are switched to the operative
position, as soon as the starting condition on sensor
inputs Y12, Y22, Y34 and 1 have been fulfilled. The
start button connection terminal Y33 is not queried.
Monitored start:
The enabling circuits are switched to the operative
position, as soon as the starting condition on sensor
inputs Y12, Y22, Y34 and 1 have been fulfilled and
the start button on terminal Y33 has subsequently
been actuated (start with the falling edge).
Ca
scade input automatic start /
monitored start
Automatic start:
The enabling circuits are switched to the operative
position, as soon as the starting condition on cascade
input 1 has been fulfilled, i.e. as soon as a static
+24 V DC signal is present (e.g. from T3).
Monitored start:
The enabling circuits are switched to the operative
position, as soon as the starting condition on cascade
input 1 has been fulfilled, i.e. as soon as a static
+24 V DC signal is present (e.g. from T3) and the start
button on terminal Y33 has subsequently been
actuated (start with the falling edge).
With / without start
-up testing
After a voltage failure, start
-up testing requires that the
sensors at Y12 and Y22 be actuated once by the system
operator.
With automatic starting / without
automatic starting after power
failure
The DM
-F Local can be parameterized, so that the
enabling circuits automatically switch to the operative
position after a power failure i.e. without pressing the
start button Y33.
Prerequisites:
Y12, Y22 or cascade input 1 are parameterized for
"monitored start".
T
he starting condition on the sensor inputs and on the
cascade input has been fulfilled.
Valid actuation of the start button prior to the power
failure i.e. the enabling circuits were in the operative
position.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals