Standard Functions
12.7 Safety Oriented Tripping
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
105
"Safe tripping" response 1)
Here, you set the SIMOCODE pro reaction to a safety-oriented tripping via the DM-F Local
or the DM-F PROFIsafe.
Note
The module response is not affected by this setting. In the event of the conditions for safety
-
oriented tripping being fulfilled, the enabling
circuits are always opened!
Response
Safe tripping
Tripping
X
Disabled
X
Send
X
Warning
X
Note
In the event that the option "DM
-F LOCAL/PROFIsafe - separate function from control
function" has been activated under "Motor control >
Control function > Operating mode",
"Tripping" can no longer be set as response; "Deactivated", "Send" or "Warning" are the only
remaining options.
Reset "Safe tripping"
Here, you can select manual or automatic acknowledging of SIMOCODE pro faults caused
by safety-oriented tripping (default: manual).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE 3UF and is the answer not in the manual?

Siemens SIMOCODE 3UF Specifications

General IconGeneral
BrandSiemens
ModelSIMOCODE 3UF
CategoryControl Systems
LanguageEnglish

Related product manuals