Online Settings and Displays
17.5 Measured Values
SIMOCODE PRO V PN FDI
148 Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
SIMOCODE pro V with a current/voltage measurement module is necessary for voltage
measurements.
Power/Power Factor
Range
Unit
Active Power P
0 to 4294967,295
W
Apparent Power S
0 to 4294967,295
VA
Cos
-phi
0 to 100
% (Power Factor. 100 % when
no motor current is flowing
and/or no voltage is
measured)
SIMOCODE pro V with a current/voltage measurement module is necessary for power
considerations.
Analog Module
Range
Unit
Analog Module
- Input 1
0 to 27648
S7
-
format: 0/4 mA=0, 20 mA =
27648
Analog Module
- Input 2
0 to 27648
S7
-
format: 0/4 mA=0, 20 mA =
27648
Analog Module
- Output
0 to 27648
S7
-
format: 0/4 mA=0, 20 mA =
27648
In the dialog box "Measured Values > Temperature module", the following values are
represented graphically.
Temperature Module
Range
Unit
Max. Temperature
-273 to 65262
°C
Temperature 1
-273 to 65262
°C
Temperature 2
-273 to 65262
°C
Temperature 3
-273 to 65262
°C
Sensor type: PT100, PT1000, KTY83, KTY84, or NTC.
SIMOCODE pro with a temperature module and corresponding temperature sensor is
necessary for temperature measurements.
In the dialog box "
Measured Values > Temperature Module", the Temperatures
Max.Temperature, Temperature 1, Temperature 2, Temperatue 3 and Sensor type PT100,
PT1000, KTY83, KTY84, or NTC and the associated measured curves are represented.
In the dialog box "
Measured Values > U(t) diagram", the phase voltages UL1-N, UL2-N and
UL3-N and the associated measured curves are represented.
In the dialog box "
Measured Values > I(t) diagram", the conductor currents I_L1, I_L2 and
I_L3 and the associated measured curves are represented.